Impact of ventilation scenario on air exchange rates and on indoor particle number concentrations in an air-conditioned classroom
Introduction
School indoor air quality (IAQ) has become a global concern as children spend the second highest percentage of their time in schools and are especially susceptible to air pollution (Leickly, 2003; USEPA, 2003). In the past several decades, exposure to indoor air pollutants has increased due to a variety of factors, including the construction of more tightly sealed buildings, reduced ventilation rates to save energy, and the use of synthetic building materials and furnishings (ALA, 2000). In addition, human activities and decisions, such as delaying maintenance to “save” money, can lead to problems from indoor sources and ventilation systems. Basically, four factors affect IAQ: sources of indoor air pollutants; the heating, ventilation, and air-conditioning (HVAC) system; pollutant pathways and occupants.
Particulate matter has been recognized as a significant cause of health problems in outdoor and indoor environments, including schools (Ransom and Pope III, 1992). Studies were conducted to understand the relationship between indoor and outdoor particulate matter concentrations in various indoor environments such as residences, offices and schools, providing an indication of how well the building envelope protects against outdoor particulate matter; or how well the building ventilation system disperses the indoor-generated particles (e.g., Lee et al., 2002; Chao et al., 2003; Li and Chen, 2003; Morawska et al., 2001, Morawska et al., 2003; Blondeau et al., 2005; Poupard et al., 2005). Most of these studies, however, were related to the IAQ under naturally ventilated conditions.
Air exchange rate (ACH) is the rate at which outdoor air replaces indoor air in a given space. Air exchange is one of several crucial, ancillary variables in understanding indoor–outdoor relationships and therefore, as such, can have an important influence on pollution levels in classrooms. If outdoor air is cleaner than indoor air, the IAQ will be improved by opening windows, turning on ceiling fans, or otherwise increasing the ACH. On the other hand, during times of high outdoor air pollution, closing the windows or otherwise reducing the ACH can have a protective effect (Anderson et al., 1999). This is particularly true for particles coming from outdoors, which deposit on walls and thus are removed from indoor air: the lower the ACH, the more particles will be removed from the air. For airborne pollutants, including particulate matter originating from both indoors and outdoors, the benefits of increasing air exchange depend on the relative intensity of pollution between indoor and outdoor air (Li and Chen, 2003). Outdoor air enters and leaves a room by infiltration, natural ventilation, and mechanical ventilation, where air movement associated with infiltration and natural ventilation is caused by air temperature differences between indoors and outdoors and by wind. In addition, there are a number of mechanical ventilation systems, ranging from outdoor-vented fans that intermittently remove air from a single room, to air handling systems that use fans and duct work to continuously remove indoor air and distribute filtered and conditioned outdoor air to strategic points throughout the room.
This study aimed to investigate the impact of ventilation scenario on ACHs and indoor particle number (PN) concentrations in an air-conditioned classroom; and to compare the IAQ in a classroom for conditions where air conditioning is the sole source of outside air or where the air conditioning is supplemented with open windows in order to increase the rate at which outdoor air is brought into the classroom. The ACHs and indoor–outdoor PN concentrations were measured in a classroom and at an oval under various scenarios of natural ventilation, mechanical ventilation and infiltration.
Section snippets
Sampling sites
The subject school is located in a small village surrounded by local residences and roads carrying a low level of local traffic (Fig. 1). The outdoor sampling site was located at the school's oval; while the indoor sampling site was in an air-conditioned classroom. The size of the classroom is about 9.60×7.25×2.70 m3 (length×width×height). The classroom is usually occupied by students during school hours on weekdays.
Instruments and parameters measured
PN concentration and size distribution in the size range from 0.014 to 0.800 μm
Indoor and outdoor PN concentrations
Table 1 presents descriptive statistical analysis of the data for PN concentrations measured in the classroom and at the oval. The overall indoor to outdoor PN ratio (I/O ratio) was recorded between 0.01 and 30.40 with a mean value of 1.28, reflecting the impact from indoor sources, meteorological conditions and the airtightness of the classroom. Detailed analysis is presented below.
Fig. 2 illustrates the time series of I/O ratio for PN for the duration of the sampling period. It can be seen
Acknowledgments
The authors thank the school for providing the classroom for measurements. In particular, we are grateful to Mrs. Melissa Conway, the teacher of the class, for her recording of activities in the classroom. The technical assistance of Dr. Graham Johnson is greatly appreciated. This project was funded by the Department of Public Works, Queensland Government.
References (19)
- et al.
Penetration coefficient and deposition rate as a function of particle size in non-smoking naturally ventilated residences
Atmospheric Environment
(2003) - et al.
Particle deposition rates in residential houses
Atmospheric Environment
(2005) - et al.
Inter-comparison of air pollutant concentrations in different indoor environment in Hong Kong
Atmospheric Environment
(2002) Children, their school environment, and asthma
Annual Allergy Asthma Immunology
(2003)- et al.
A balance-point method for assessing the effect of natural ventilation on indoor particle concentrations
Atmospheric Environment
(2003) - et al.
The relationship between indoor and outdoor airborne particles in the residential environment
Atmospheric Environment
(2001) - et al.
Characteristics of particle number and mass concentrations in residential houses in Brisbane, Australia
Atmospheric Environment
(2003) - et al.
Statistical analysis of parameters influencing the relationship between outdoor and indoor air quality in schools
Atmospheric Environment
(2005) - et al.
Elementary school absences and PM-10 pollution in Utah Valley
Environmental Research
(1992)
Cited by (131)
Air infiltration rate distribution across Chinese five climate zones: A modelling study for rural residences
2024, Building and EnvironmentComparison of pollen indoor/outdoor ratios during off-peak and peak periods in Japan
2023, Building and EnvironmentModeling impacts of ventilation and filtration methods on energy use and airborne disease transmission in classrooms
2022, Journal of Building EngineeringInfluence of various factors on indoor/outdoor pollen concentration ratio based on experimental research: A review
2022, Building and Environment
- 1
Presently at the Department of Civil and Structural Engineering, The Hong Kong Polytechnic University, Hong Kong.