Volume 42, Issue 4, February 2008, Pages 757-768
Atmospheric Environment

Impact of ventilation scenario on air exchange rates and on indoor particle number concentrations in an air-conditioned classroom

https://doi.org/10.1016/j.atmosenv.2007.09.070Get rights and content

Abstract

A 2-week intensive measurement campaign of indoor and outdoor air pollution was carried out in September 2006, in a primary school to investigate indoor–outdoor correlations of particle number (PN) concentrations, and the impact of air exchange rate (ACH) on the indoor PN concentration. The ACHs in the classroom for different conditions associated with window opening and the operational status of air conditioners (A/C) and fans were tested. As expected, the lowest ACH (0.12 h−1) was found when the windows were closed and A/C and fans were off. In contrast, the highest ACH (7.92 h−1) was observed when the windows were opened and A/C and fans were all on. The analysis of the PN I/O ratios at different ACHs in the absence of indoor sources indicates that the mean I/O ratio was 0.621±0.007 (mean±95% confidence interval) when the windows were closed, and A/C and fans were off; 0.524±0.023 when windows were closed, fans were off and A/C was on; and 0.502±0.029 when windows were closed, A/C was off and fans were on. To further understand the relationship between indoor and outdoor PN concentrations, the impact of outdoor PN concentration on I/O ratios at different ACHs was investigated. It was found that the relationship between outdoor PN concentration and the I/O ratio at different ACHs followed a power trendline with an equation of I/O ratio=A PNout−b (A and b are coefficients, PNout is outdoor PN concentration), suggesting that the penetration efficiency decreased with increasing outdoor PN concentration. It is the first time we found that when the outdoor PN concentration increased there was an associated increase in the concentration of nano-particles, which have been demonstrated to have higher deposition rates and lower penetration efficiencies. Based on the above equation, the study also showed a significant effect of ACH on indoor PN concentrations under stable outdoor PN concentrations. In general, the higher the ACH was, the lower the indoor PN concentration was.

Introduction

School indoor air quality (IAQ) has become a global concern as children spend the second highest percentage of their time in schools and are especially susceptible to air pollution (Leickly, 2003; USEPA, 2003). In the past several decades, exposure to indoor air pollutants has increased due to a variety of factors, including the construction of more tightly sealed buildings, reduced ventilation rates to save energy, and the use of synthetic building materials and furnishings (ALA, 2000). In addition, human activities and decisions, such as delaying maintenance to “save” money, can lead to problems from indoor sources and ventilation systems. Basically, four factors affect IAQ: sources of indoor air pollutants; the heating, ventilation, and air-conditioning (HVAC) system; pollutant pathways and occupants.

Particulate matter has been recognized as a significant cause of health problems in outdoor and indoor environments, including schools (Ransom and Pope III, 1992). Studies were conducted to understand the relationship between indoor and outdoor particulate matter concentrations in various indoor environments such as residences, offices and schools, providing an indication of how well the building envelope protects against outdoor particulate matter; or how well the building ventilation system disperses the indoor-generated particles (e.g., Lee et al., 2002; Chao et al., 2003; Li and Chen, 2003; Morawska et al., 2001, Morawska et al., 2003; Blondeau et al., 2005; Poupard et al., 2005). Most of these studies, however, were related to the IAQ under naturally ventilated conditions.

Air exchange rate (ACH) is the rate at which outdoor air replaces indoor air in a given space. Air exchange is one of several crucial, ancillary variables in understanding indoor–outdoor relationships and therefore, as such, can have an important influence on pollution levels in classrooms. If outdoor air is cleaner than indoor air, the IAQ will be improved by opening windows, turning on ceiling fans, or otherwise increasing the ACH. On the other hand, during times of high outdoor air pollution, closing the windows or otherwise reducing the ACH can have a protective effect (Anderson et al., 1999). This is particularly true for particles coming from outdoors, which deposit on walls and thus are removed from indoor air: the lower the ACH, the more particles will be removed from the air. For airborne pollutants, including particulate matter originating from both indoors and outdoors, the benefits of increasing air exchange depend on the relative intensity of pollution between indoor and outdoor air (Li and Chen, 2003). Outdoor air enters and leaves a room by infiltration, natural ventilation, and mechanical ventilation, where air movement associated with infiltration and natural ventilation is caused by air temperature differences between indoors and outdoors and by wind. In addition, there are a number of mechanical ventilation systems, ranging from outdoor-vented fans that intermittently remove air from a single room, to air handling systems that use fans and duct work to continuously remove indoor air and distribute filtered and conditioned outdoor air to strategic points throughout the room.

This study aimed to investigate the impact of ventilation scenario on ACHs and indoor particle number (PN) concentrations in an air-conditioned classroom; and to compare the IAQ in a classroom for conditions where air conditioning is the sole source of outside air or where the air conditioning is supplemented with open windows in order to increase the rate at which outdoor air is brought into the classroom. The ACHs and indoor–outdoor PN concentrations were measured in a classroom and at an oval under various scenarios of natural ventilation, mechanical ventilation and infiltration.

Section snippets

Sampling sites

The subject school is located in a small village surrounded by local residences and roads carrying a low level of local traffic (Fig. 1). The outdoor sampling site was located at the school's oval; while the indoor sampling site was in an air-conditioned classroom. The size of the classroom is about 9.60×7.25×2.70 m3 (length×width×height). The classroom is usually occupied by students during school hours on weekdays.

Instruments and parameters measured

PN concentration and size distribution in the size range from 0.014 to 0.800 μm

Indoor and outdoor PN concentrations

Table 1 presents descriptive statistical analysis of the data for PN concentrations measured in the classroom and at the oval. The overall indoor to outdoor PN ratio (I/O ratio) was recorded between 0.01 and 30.40 with a mean value of 1.28, reflecting the impact from indoor sources, meteorological conditions and the airtightness of the classroom. Detailed analysis is presented below.

Fig. 2 illustrates the time series of I/O ratio for PN for the duration of the sampling period. It can be seen

Acknowledgments

The authors thank the school for providing the classroom for measurements. In particular, we are grateful to Mrs. Melissa Conway, the teacher of the class, for her recording of activities in the classroom. The technical assistance of Dr. Graham Johnson is greatly appreciated. This project was funded by the Department of Public Works, Queensland Government.