TY - JOUR T1 - Investigation of air change rate and aerosol behavior during an outbreak of COVID-19 in a geriatric care facility JF - medRxiv DO - 10.1101/2022.01.27.22269512 SP - 2022.01.27.22269512 AU - Yo Ishigaki AU - Shinji Yokogawa AU - Yuki Minamoto AU - Akira Saito AU - Hiroko Kitamura AU - Yuto Kawauchi Y1 - 2022/01/01 UR - http://medrxiv.org/content/early/2022/03/01/2022.01.27.22269512.abstract N2 - Background Ventilation plays an important role in controlling aerosol transmission of coronavirus disease (COVID-19), and mass transmission of COVID- 19 has been reported in poorly ventilated areas.Objective A real-world mass infection outbreak which occurred in an elderly nursing home, in Miyagi Prefecture, Japan, was simulated experimentally and numerically to investigate the controlling factors and quantify the effectiveness of various natural ventilation settings by means of air change rate (ACR).Methods Using the CO2 tracer gas method, the ACR values at the time of the outbreak were estimated to be 2.0–6.2 h-1 in rooms in the facility. Furthermore, a low-cost intervention of opening windows improved the ventilation frequency by a factor of 1.48–5.74. This implies that advective fluid flows are the key in the spread of high CO2 concentration zones. A numerical simulation was performed to obtain spatio-temporal evolution on such high CO2 concentration zones under similar conditions to the present experiment.Results The results showed that ventilation was significantly dependent on the window opening conditions in all rooms (p-values ranging from 0.001 to 0.03 for all the rooms). In contrast, there was no significant dependence on the location of the sensor in any of the areas. Development of high CO2 concentration zones occurs in the first few minutes. Furthermore, the leading edge of such zones towards the common room yields a relatively high fluid velocity, suggesting that the large-scale advective flow dictates the spread of such high CO2 concentration zones.Conclusions The present results suggest that secondary infections could occur due to the aerosol advection driven by such large-scale flows, even when the building design adheres the ventilation guidelines. In elderly care facilities, open architectural spaces are recommended to realize quality of life and monitor residents. However, management is required to reduce the downwind infection risk from aerosols and ACR.Competing Interest StatementThe authors have declared no competing interest.Funding StatementThis work was supported by JSPS KAKENHI Grant No. 21K19820 and KDDI foundation.Author DeclarationsI confirm all relevant ethical guidelines have been followed, and any necessary IRB and/or ethics committee approvals have been obtained.YesThe details of the IRB/oversight body that provided approval or exemption for the research described are given below:This study was approved by the Ethics Committee on Experiments on Human Subjects in the Corresponding author's institution (the University of Electro-Communications, Tokyo, Japan). The approval number is 21005.I confirm that all necessary patient/participant consent has been obtained and the appropriate institutional forms have been archived, and that any patient/participant/sample identifiers included were not known to anyone (e.g., hospital staff, patients or participants themselves) outside the research group so cannot be used to identify individuals.YesI understand that all clinical trials and any other prospective interventional studies must be registered with an ICMJE-approved registry, such as ClinicalTrials.gov. I confirm that any such study reported in the manuscript has been registered and the trial registration ID is provided (note: if posting a prospective study registered retrospectively, please provide a statement in the trial ID field explaining why the study was not registered in advance).YesI have followed all appropriate research reporting guidelines and uploaded the relevant EQUATOR Network research reporting checklist(s) and other pertinent material as supplementary files, if applicable.YesAll data produced in the present study are available upon reasonable request to the authorsAbbreviationsACRair change rate per hourCDCCenters for Disease Control and PreventionMHLWMinistry of Health, Labor and WelfareWHOWorld Health Organization ER -